35 changes: 34 additions & 1 deletion ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -1783,6 +1783,20 @@ RHHC:
- return_air_relative_humidity_sensor
- return_air_relative_humidity_setpoint

EDHC:
guid: "d15d63a4-9fea-49f9-a0eb-9399012cbe93"
description: "Exhaust air humidification/dehumidification control."
is_abstract: true
opt_uses:
- humidification_percentage_command
- failed_humidifier_alarm
uses:
- dehumidification_run_command
- humidification_run_command
- exhaust_air_relative_humidity_sensor
- exhaust_air_relative_humidity_setpoint
implements:
- OPERATIONAL

SHC:
guid: "c27f33dc-19bc-47f4-937a-eab3293b920f"
Expand Down Expand Up @@ -7051,6 +7065,15 @@ OCWRWISOVPM:
implements:
- MONITORING

OCWSWISOVPM:
guid: "751499e7-56c7-4ec2-8edd-d642c8e9d653"
description: "Open-loop CDW supply side isolation valve percentage control."
is_abstract: true
uses:
- outside_condensing_loop_supply_water_isolation_valve_percentage_command
- outside_condensing_loop_supply_water_isolation_valve_percentage_sensor
implements:
- MONITORING

HWRWISOVM:
guid: "a2ca0c24-c44d-44ea-95cb-728da67d7c78"
Expand Down Expand Up @@ -8437,6 +8460,16 @@ CPC2X:
- failed_circulation_pump_alarm_1
- failed_circulation_pump_alarm_2

OCWCPC2X:
guid: "c1a4812d-d458-48ae-9fb9-cb92048ab6c9"
description: "Circulation control for 2 open loop condenser water pumps."
is_abstract: true
uses:
- outside_condensing_loop_water_circulation_pump_run_command_1
- outside_condensing_loop_water_circulation_pump_run_command_2
- outside_condensing_loop_water_circulation_pump_run_status_1
- outside_condensing_loop_water_circulation_pump_run_status_2

SDHC:
guid: "de065843-b1a9-4d2e-b751-31d7af8e8991"
description: "Supply dehumidification control with a temperature setpoint."
Expand All @@ -8451,7 +8484,7 @@ SDHC:
- leaving_dehumidifier_temperature_sensor
- leaving_dehumidifier_temperature_setpoint
implements:
- CONTROL
- CONTROL

FPHC:
guid: "bdd89332-3303-420d-a13c-ee38c398d9ff"
Expand Down
8 changes: 8 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/DMP.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -99,6 +99,14 @@ DMP_ZSPC_EFM:
- ZSPC
- EFM

DMP_OAFC:
guid: "35d72afa-47e3-48ba-8f59-51c74ebbbddd"
description: "Stand-alone damper with outside air flowrate control."
is_canonical: true
implements:
- DMP
- OAFC

###################################
### Existing Non-standard Types ###
###################################
Expand Down
14 changes: 14 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/HX.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -158,6 +158,20 @@ HX_CWRWISOVPM_OCWRWISOVPM_CWTWRTM:
- condensing_return_water_temperature_sensor
- outside_condensing_loop_return_water_temperature_sensor

HX_CWSWISOVPM_OCWSWISOVPM_CWBYPVPM_OCWCPC2X_CWTWSTM:
guid: "c6982fd1-9301-4c91-b4a9-1b359ff1b17c"
description: "Heat exchanger between closed-loop condensing water and open-loop (tower) water with circulation pumps."
is_canonical: true
implements:
- HX
- CWSWISOVPM
- OCWSWISOVPM
- CWBYPVPM
- OCWCPC2X
uses:
- condensing_supply_water_temperature_sensor
- outside_condensing_loop_supply_water_temperature_sensor

HX_RWISOVM:
guid: "2385f180-c38d-48a1-9604-1d822dfe99ff"
description: "Simple return water isolating heat exchanger."
Expand Down
21 changes: 21 additions & 0 deletions ontology/yaml/resources/fields/telemetry_fields.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -2862,6 +2862,15 @@ literals:
- outside_condensing_loop_return_water_temperature_sensor:
flexible_min: 255.9259259
flexible_max: 308.1481481
- outside_condensing_loop_supply_water_isolation_valve_percentage_command:
fixed_min: 0.0
fixed_max: 100.0
- outside_condensing_loop_supply_water_isolation_valve_percentage_sensor:
fixed_min: 0.0
fixed_max: 100.0
- outside_condensing_loop_supply_water_temperature_sensor:
flexible_min: 255.9259259
flexible_max: 308.1481481
- transducer_failed_alarm:
- ACTIVE
- INACTIVE
Expand Down Expand Up @@ -3763,6 +3772,12 @@ literals:
- condensing_water_circulation_pump_run_status:
- ON
- OFF
- outside_condensing_loop_water_circulation_pump_run_command:
- ON
- OFF
- outside_condensing_loop_water_circulation_pump_run_status:
- ON
- OFF
# Four fields below are for ASHP.
- heating_run_command:
- ON
Expand Down Expand Up @@ -3944,6 +3959,12 @@ literals:
- supply_air_damper_voltage_sensor:
flexible_min: 0.0
flexible_max: 120.0
- exhaust_air_relative_humidity_sensor:
fixed_min: 0.0
fixed_max: 100.0
- exhaust_air_relative_humidity_setpoint:
fixed_min: 0.0
fixed_max: 100.0
- glycol_differential_pressure_sensor:
flexible_min: -34473.78945
flexible_max: 344737.8945
Expand Down