IBEM Current Calibration

Dave Williams | DitroniX | G8PUO edited this page Mar 23, 2024 · 7 revisions

The IBEM board has dual parallel current sensors which are fed into separate ADS1115 channels, to provide an amalgamated current.

A single DC Current Offset is provided to easily 'zero' the current, whilst maintaining linear current readings.

The simple process to calibrate the current on your board is:

  1. Connect the board to the battery system but disconnect and chargers/inverters etc.
  2. Take a current reading using the software serial monitor, OLED display or the web interface.
  3. Enter the 'current' value into the DCCurrentOffset.
  4. Reflash and calibration is complete.

Read the Zero Current value (in our example it is -1.70A) OLED Example

Web Page Example

Update the the DCCurrentOffset value (Example from 0.00A to -1.70A) Default Value

Updated Value

After Flashing - Validate the the DCCurrentOffset value is correct Validate Reading at Zero Current Flow